150
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 6
CGCM-DLR Unit Software Interface
Data Table
Table 10 - Output (scheduled write) Data Table, Assembly Instance 1
Byte
Size in
Bytes
Type
Bits
Tag Name
Description
Units
Range
0
1
BOOL
0
RevVARFltOutEn
Reverse VAR Fault Output Enable
-
0 = Disabled,
1 = Enabled
BOOL
1
RevPwrFltOutEn
Reverse Power Fault Output Enable
BOOL
2
OvrExcFltOutEn
Over-excitation Fault Output Enable
BOOL
3
Ovr_I_FltOutEn
Over-current Fault Output Enable
BOOL
4
Undr_V_FltOutEn
Undervoltage Fault Output Enable
BOOL
5
Ovr_V_FltOutEn
Overvoltage Fault Output Enable
BOOL
6
UndrFreqFltOutEn
Under-frequency Fault Output Enable
BOOL
7
OvrFreqFltOutEn
Over-frequency Fault Output Enable
1
1
BOOL
0
Spare1
-
-
BOOL
1
LossExcFltOutEn
Loss Excitation Fault Output Enable
0 = Disabled,
1 = Enabled
BOOL
2
OEL_En
Over-excitation Limiting Enable
BOOL
3
UEL_En
Under-excitation Limiting Enable
BOOL
4
LossSensingFltOutEn
Loss Sensing Fault Output Enable
BOOL
5
LossPMGFLtOutEn Loss
Permanent Magnet Generator
Fault Output Enable
BOOL
6
RotDiodeFltOutEn
Rotation Diode Fault Output Enable
BOOL
7
PhRotFltOutEn
Phase Rotation Fault Output Enable
2
1
BOOL
0
Spare2
-
-
BOOL
1
Spare3
BOOL
2
EngineIdle
Engine Idle
0 = False, 1 = True
BOOL
3
Spare4
BOOL
4
PF_VAR_Select
Power Factor/VAR Select
0 = PF, 1 = VAR
BOOL
5
PF_VAR_En
Power Factor/VAR Enable
0 = Disabled,
1 = Enabled
BOOL
6
AVR_FCR_Select Automatic
Voltage
Regulator/Field
Current Regulator Select
0 = AVR, 1 = FCR
BOOL
7
FltReset
Fault Reset
0 = De-assert,
1 = Assert
3
1
BOOL
0
AutoSyncEn
Auto Synchronization Enable
-
0 = Disabled,
1 = Enabled
BOOL
1
CheckSyncEn
Check Synchronization Enable
BOOL
2
PermissiveSyncEn Permissive Synchronization Enable
BOOL
3
Spare5
BOOL
4
Spare6
BOOL
5
Bus A_B_Select
Bus A/B Select
0 = Bus A, 1 = Bus B
BOOL
6
DeadBusClosureEn
Dead Bus Closure Enable
0 = Disabled,
1 = Enabled
BOOL
7
InitiateSync
Initiate Synchronization
0 = Inactive, 1 = Active