Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
179
Time Over-current Characteristic Curves
Appendix
A
Time Dial Setting Cross-reference
Although the time characteristic curve shapes have been optimized for each relay,
time dial settings of the CGCM-DLR unit are not identical to the settings of
electromechanical induction disk over-current relays.
The
Characteristic Curve Cross-reference
table on
helps you convert
the time dial settings of induction disk relays to the equivalent setting for the
CGCM-DLR unit.
Using Table
Inspection of published electromechanical time current characteristic curves
provide the cross-reference table values. The time delay for a current of five times
tap was entered into the time dial calculator function for each time dial setting.
The equivalent CGCM-DLR unit time dial setting was then entered into the
cross-reference table.
If your electromechanical relay time dial setting is between the values that are
provided in the table, it is necessary to interpolate (estimate the correct
intermediate value) between the electromechanical setting and the default
configuration.
Table 36 - Characteristic Curve Cross-reference
Curve
Curve Name
Page
Similar To
1
S, Short Inverse
ABB CO-2
2
S2, Short Inverse
GE IAC-55
3
L, L1, Long Inverse
ABB CO-5
4
L2, Long Inverse
GE IAC-66
5
D, Definite Time
ABB CO-6
6
M, Moderately Inverse
ABB CO-7
7
I, I1 Inverse Time
ABB CO-8
8
I2 Inverse Time
GE IAC-51
9
V, V1 Very Inverse
ABB CO-9
10
V2, Very Inverse
GE IAC-53
11
E, E1 Extremely Inverse
ABB CO-11
12
E2, Extremely Inverse
GE IAC-77
13
A Standard Inverse
BS, IEC Standard Inverse
14
B, Very Inverse (It)
BS, IEC Very Inverse (I
2
t)
15
Extremely Inverse (I
2
t)
BS, IEC Extremely Inverse (I
2
t)
16
Long Time Inverse
BS, IEC Long Time Inverse
17
Fixed Time
N/A
N/A