Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
215
Specifications
Appendix
D
Loss of PMG
Reverse VAR
Over/Under-frequency
Reverse Power
Rotating Diode Monitor - Range
Attribute
Value
Pickup
< 10V AC single-phase,
< 50V AC 3-phase or an imbalance
greater than 20%
Response time
< 400 ms
Attribute
Range
Increment
Accuracy
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Range
Increment
Accuracy
Pickup
30…70 Hz
0.01 Hz
±2% Hz
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Range
Increment
Accuracy
Pickup
1…100% of rated
generator VA
1%
±0.5% rated VA
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Value
Number of generator poles
0…24
Number of brushless exciter poles
0…24
Increment
2
Fault time delay (applies to both open and
shorted diode conditions)
0.1…300 s