Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
209
Appendix
D
Specifications
The CGCM-DLR unit electrical and physical characteristics are listed in the
following tables.
Control Power
Waste Electrical and Electronic Equipment (WEEE)
Excitation Power
Supply
Burden
18…32V DC (24V DC nom)
(A 24V Nominal Battery or 24V DC Power Supply
with ATEX certification powers the unit.)
30 W
AC ripple, max
50%, 50…120 Hz
At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.
Source
Phases
Wiring Configuration
Voltage
Frequency
VA (Max)
PMG
(1)
Single-phase
PMG-A and PMG-C
Min 56 Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
PMG
3-phase
Floating Wye
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
(2)
Single-phase
PMG-A and PMG-C
Min 56 Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Floating Wye
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Grounded Wye
(grounded neutral)
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Floating delta
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Open delta, floating
Min 56 Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
(1) PMG = Permanent Magnet Generator.
(2) SE = Separately Excited.