Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
211
Specifications
Appendix
D
Bus Voltage Sensing
Auxiliary Input
Communication Ports
Phase
Wiring
Configurations
Grounded
Connection
Available
Voltage
Frequency
Single-phase
V Bus A and
V Bus C
No
Min 57 Vrms
Max 150 Vrms
Min 20 Hz
Max 90 Hz
Three-phase
Floating Wye
No
Min 99 Vrms L-L
Max 208 Vrms L-L
Min 20 Hz
Max 90 Hz
Three-phase
Grounded Wye
(grounded neutral)
Yes
Min 99 Vrms L-L
Max 208 Vrms L-L
Min 20 Hz
Max 90 Hz
Three-phase
Open delta, grounded
B phase
Yes
Min 99 Vrms L-L
Max 150 Vrms L-L
Min 20 Hz
Max 90 Hz
Attribute
Value
Range
-10…10V DC
Input impedance
20 k
Ω
Attribute
Value
EtherNet/IP
®
DLR network
EtherNet/IP Device Level Ring, dual RJ45
network interface jacks
Redundancy port
DB9 Connector, 9600 bps, 8N1 (For redundant
CGCM-DLR unit use only.)
Factory port
DB15 Connector, 9600 bps, 8N1 (Not for
customer use.)