Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
147
CGCM-DLR Unit Software Interface
Chapter 6
8
1
BOOL
0
Activebus_A_B
Bus A/B Active
-
0=Bus A,
1=Bus B
BOOL
1
Raise_V Raise
Voltage
0=False,
1=True
BOOL
2
Lower_V Lower
Voltage
BOOL
3
Raise_Freq Raise
Frequency
BOOL
4
Lower_Freq Lower
Frequency
BOOL
5
Raise_Ph Raise
Phase
BOOL
6
Lower_Ph Lower
Phase
BOOL
7
SyncFailure Synchronization
Failure
9
1
BOOL
0
AutoSync
Auto Synchronization Enabled
-
0=Disabled,
1=Enabled
BOOL
1
CheckSync
Check Synchronization Enabled
BOOL
2
PermissiveSync
Permissive Synchronization Enabled
BOOL
3
UndefinedSyncMode
Undefined Synchronization Mode
0=No, 1=Yes
BOOL
4
SyncModeConflict Synchronization
Mode
Conflict
BOOL
5
SyncDeadBus
Dead Bus Synchronization
BOOL
6
CloseBusA_Brkr
Close Bus A Breaker
0=Don’t Close,
1=Close
BOOL
7
CloseBusB_Brkr
Close Bus B Breaker
10
1
BOOL
0
Spare2
Indicates when the excitation output
short-circuit protection is active.
-
0 = Inactive
1 = Active
BOOL
1
FreqLessThan10Hz
Frequency Less Than 10 Hz
0=False, 1=True
BOOL
2
Spare3
BOOL
3
SetptTraverseActive Traverse
Setpoint
Active
0=Setpoint,
1=Traverse
BOOL
4
ShortedRotDiodeFlt
Rotating Diode Shorted Fault
0=Inactive, 1=Active
BOOL
5
OpenRotDiodeFlt
Rotating Diode Open Fault
BOOL
6
HardwareExcEned Hardware
Excitation
Enabled
0=Disabled,
1=Enabled
BOOL
7
SoftwareExcEned
Software Excitation Enabled
11
1
BOOL
0
ConfigRcvd
Configuration Received
-
0=False
1=True
BOOL
1
UnschdWriteRcvd
Unscheduled Write Received
BOOL
2
Spare6
BOOL
3
Spare7
BOOL
4
Spare8
BOOL
5
kVAR_LS_Active
Reserved for future use
BOOL
6
Spare9
BOOL
7
kW_LS_Active
kW Load Share Active
0=Inactive 1=Active
12
4
Real
N/A
Total_kW
Total kW
kW
-3E+09…3E+09
16
4
Real
N/A
LS_Err
Load Share Error
%
-1.00…1.00
20
4
Real
N/A
kW_LS_InputV
kW Load Share Input Voltage
Volts
0…5
24
4
Real
N/A
kW_PU_Load
kW Load Per Unit
-
0…5
Table 7 - Scheduled Read Data Table
Byte
Size in
Bytes
Type
Bits
Tag Name
Descr
Units
Range