Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 4
CGCM-DLR Unit Configuration
Related Parameters
•
GenRatedExcI
•
OEL_En
tag in the Output table
UEL Page
The UEL tab is used to configure the unit settings that are related to operation of
the Under-excitation Limiting (UEL) function. The values that are entered in
this tab establish break points in a piecewise linear curve that defines the
characteristic curve for this function. See the generator manufacturer data for the
proper setting information.
See
for more information on the operation of the UEL function.
•
Under-excitation Limiting Enable – Select this checkbox to enable
over-excitation limiting, which sets the
UEL_En
tag in the configuration
table. Tag
UEL_En
in the configuration table stores this parameter. The
UEL_En
tag in the Output (Scheduled Write) Data table must also be set
to enable this function.