158
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 6
CGCM-DLR Unit Software Interface
The Set Attributes Single
service for instance 4 of the Assembly Object can access
the following information.
Configuration Checking
When configuration data is received, the CGCM-DLR unit verifies that
individual parameters are within the minimum and maximum values that are
indicated in
(for example, perform range checking). If an out-of-range
parameter is detected, the CGCM-DLR unit enters a configuration fault mode
and ignores all data in the configuration write. The Connection tab in the
module configuration dialog box in the Logix Designer application displays an
error code that corresponds to the first offending configuration parameter. The
CGCM-DLR unit
does not
perform any application checks (for example, is a
value suitable for the particular application) or dependency checks (for example,
is a value reasonable based on other values entered).
Data Table
Table 17 - Set Attributes Single (Service Code 0x10)
Name Attribute
ID Data
Type
Value
Data 3
UINT
See Unscheduled Configuration Read/
Write Data Table, Assembly Instance 4
IMPORTANT
Use of this service is not recommended. Writing the CGCM-DLR unit
configuration with unscheduled messaging is not recommended. We
recommend that you use only scheduled configuration messaging that is sent
when the connection is opened or the module configuration is edited in the
Logix Designer application.
Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4
Byte
Size in
Bytes
Type
Bits
Tag Name
Description
Units
Range
Error Code
0
1
SINT
N/A
Space Reserved for Logix controller Revision Configuration Number
1
3
SINT
N/A
Pad Bytes Reserved for Logix controller Usage
4
1
BOOL
0
RevVARFltOutEn
Reverse VAR Fault Output Enable
-
0=Disabled,
1=Enabled
BOOL
1
RevPwrFltOutEn
Reverse Power Fault Output
Enable
BOOL
2
OvrExcFltOutEn
Over-excitation Fault Output
Enable
BOOL
3
Ovr_I_FltOutEn
Over-current Fault Output Enable
BOOL
4
Undr_V_FltOutEn
Undervoltage Fault Output
Enable
BOOL
5
OvrVFltOutEn
Overvoltage Fault Output Enable
BOOL
6
UndrFreqFltOutEn
Under-frequency Fault Output
Enable
BOOL
7
OvrFreqFltOutEn
Over-frequency Fault Output
Enable