250
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix F
Configuration Record Worksheet
Figure 71 - Offline Over-excitation Limiting
Figure 72 - Online Over-excitation Limiting
Table 49 - Over-excitation Limiting (OEL) Tab
Parameter
Units
Setting
Online high-level setpoint
A DC
Online high-level time delay
s
Online medium-level setpoint
A DC
Online medium-level time delay
s
Online low-level setpoint
A DC
Offline high-level setpoint
A DC
Offline high-level time delay
s
Offline low-level setpoint
A DC
FIELD
C
URRENT
TIME IN
S
ECOND
S
High
Current
Time
CONTINUOU
S
0…10 seconds
Low
Current
Level
0…15 A dc
High
Current
Level
0…30 A dc
FIELD CURRENT
TIME IN
S
ECOND
S
High
Current
Time
0…10 seconds
CONTINUOU
S
Medium
Current
Time
0…120 seconds
Low
Current
Level
0.0…15 A dc
Medium
Current
Level
0.0… 20 A dc
High
Current
Level
0.0…30 A dc