Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 6
CGCM-DLR Unit Software Interface
Unscheduled Write Data Table
The Unscheduled Write data table contains gains and other configuration
parameters that can be written to the CGCM-DLR unit by the ControlLogix
controller regardless of the excitation state.
The host controller writes the data in this Controller Tag from the unit by using
unscheduled messaging that is controlled by the user program.
Data Type
The Unscheduled Write data table is automatically created by using the
appropriate module-defined data type.
76
4
Real
PhAB_GenV
Phase AB Generator Voltage
V
0…30,000
80
4
Real
PhBC_GenV
Phase BC Generator Voltage
84
4
Real
PhCA_GenV
Phase CA Generator Voltage
88
4
Real
AvgLN_GenV
Average LN Generator Voltage
92
4
Real
PhA_GenV
Phase A Generator Voltage
96
4
Real
PhB_GenV
Phase B Generator Voltage
100
4
Real
PhC_GenV
Phase C Generator Voltage
104
4
Real
AvgLL_BusV
Average LL Bus A Voltage
108
4
Real
PhAB_BusV
Phase AB Bus A Voltage
112
4
Real
PhBC_BusV
Phase BC Bus A Voltage
116
4
Real
PhCA_BusV
Phase CA Bus A Voltage
120
4
Real
AvgLN_BusV
Average LN Bus A Voltage
124
4
Real
PhA_BusV
Phase A Bus A Voltage
V
0…30000
128
4
Real
PhB_BusV
Phase B Bus A Voltage
132
4
Real
PhC_BusV
Phase C Bus A Voltage
136
4
Real
BusB_V
Bus B Voltage
140
4
Real
Exc_V
Excitation Voltage
0
200
144
4
Real
Exc_I
Excitation Current
Amps
0
15
148
4
Real
ExcRipple
Excitation Ripple Current
Amps/%
0
15
152
4
Real
kW_Hrs
kW Hours
kWh
-3.04 * 10
38
3.04 * 10
38
156
4
Real
kVAR_Hrs
kVAR Hours
kVARh
-3.04 * 10
38
3.04 * 10
38
160
4
Real
kVA_Hrs
kVA Hours
kVAh
0
3.04 * 10
38
164
4
Real
V_AdjustOffset
Voltage Adjust Offset
%
-10
10
168
2
INT
Spare
170
2
INT
Resvd
Reserved
Table 12 - Unscheduled Read Data Table, Assembly Instance 5
Byte
Size in
Bytes
Type
Tag Name
Description
Units
Range