148
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 6
CGCM-DLR Unit Software Interface
28
4
Real
N/A
kW_AnalogPU_Load
kW Analog Value Per Unit
-
0…1
32
4
Real
N/A
kVAR_LS_InputV
kVAR Load Share Input Voltage
Volts
0…1
36
4
Real
N/A
kVAR_PU_load
kVAR Load Per Unit
-
40
4
Real
N/A
kVAR_AnalogPU_Load
kVAR Analog Value Per Unit
-
0…1
44
4
Real
N/A
AvgLLGenV
Average Generator LL Voltage
Volts
0…30,000
48
4
Real
N/A
V_MatchErr
Voltage Match Error
%V
-100…100
52
4
Real
N/A
FreqMatchErr
Frequency Match Error
Hz
-90…90
56
4
Real
N/A
PhMatchErr
Phase Match Error
Deg
-180…180
60
4
Real
N/A
GenFreq
Generator Frequency
Hz
10…90
64
4
Real
N/A
BusFreq
Active Bus Frequency
Hz
10…90
68
4
Real
N/A
Spare10
-
72
4
Real
N/A
Spare11
-
Table 7 - Scheduled Read Data Table
Byte
Size in
Bytes
Type
Bits
Tag Name
Descr
Units
Range