CGCM-DLR Unit Operation
Limiting Functions
This section discusses the different types of limiting functions the CGCM-DLR
unit provides.
•
•
•
Generator Capability Curve
The generator capability curve graphically depicts the combinations of real and
reactive power a generator is able to produce (or absorb, in the case of reactive
power) without damage that is caused by overheating. The CGCM-DLR unit
provides a number of limiting functions that are designed to maintain operation
within safe areas of the generator capability curve.
A typical generator capability curve is shown in the following illustration.
Figure 30 - Typical Generator Capability Curve
1.0
0.8
0.6
0.4
0.2
0.0
-0.2
-0.4
-0.6
-0.8
-1.0
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Lagging
Leading
Reactive Power
, per Unit
Rating PF
Lagging
Armature Winding
Heating Limitation
Prime Mover
Power Limitation
95% PF
Leading
Armature Core
End Iron Heating
Limitation
Field Winding
Heating Limitation
Real Power, per Unit