146
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 6
CGCM-DLR Unit Software Interface
Table 7 - Scheduled Read Data Table
Byte
Size in
Bytes
Type
Bits
Tag Name
Descr
Units
Range
0
4
DINT
0…7
Status_32_bit
Connect Status
4
1
BOOL
0
RevVARFlt
Reverse kVAR Fault
-
0=Inactive, 1=Active
BOOL
1
RevPwrFlt
Reverse kW Fault
BOOL
2
OvrExcFlt
Over-excitation Fault
BOOL
3
Ovr_I_Flt
Over-current Fault
BOOL
4
Undr_V_Flt
Undervoltage Fault
BOOL
5
Ovr_V_Flt
Overvoltage Fault
BOOL
6
UndrFreqFlt
Under-frequency Fault
BOOL
7
OvrFreqFlt
Over-frequency Fault
5
1
BOOL
0
CGCM_Flt
CGCM-DLR Internal Fault
-
0=Inactive, 1=Active
BOOL
1
LossExcFlt
Loss of Excitation Current Fault
BOOL
2
OEL_Active
Over-excitation Limiting Active
BOOL
3
UEL_Active
Under-excitation Limiting Active
BOOL
4
LossSensingFlt
VT Sensing Loss
BOOL
5
LossPMGFlt
PMG Loss
BOOL
6
RotDiodeFlt
Rotating Diode Fault
BOOL
7
PhRotFlt
Phase Rotation Fault
6
1
BOOL
0
BusRot_ABC_ACB
Rotation Bus
-
0=ABC, 1=ACB
BOOL
1
GenRot_ABC_ACB
Rotation Generator
BOOL
2
FltOut
Output Active Fault
0=Inactive, 1=Active
BOOL
3
ExcOut
Excitation Out Enabled
0=Disabled,
1=Enabled
BOOL
4
PF_VAR_Selection
Power Factor/VAR Selection
0=PF, 1=VAR
BOOL
5
PF_VAR_Control_Ened
Power Factor/VAR Control Enabled
0=Disabled,
1=Enabled
BOOL
6
AVR_FCR_Selection
AVR/FCR Control Selection
0=AVR, 1=FCR
BOOL
7
FLTResetAck
Reset Acknowledge Fault
0=No, 1=Yes
7
1
BOOL
0
BusV_Present
Bus Voltage Present
-
0=False, 1=True
BOOL
1
GenV_Present Generator
Voltage
Present
BOOL
2
PhRotMatch Phase
Rotation
Match
BOOL
3
V_Match Voltage
Match
BOOL
4
FreqMatch Frequency
Match
BOOL
5
PhMatch Phase
Match
BOOL
6
CGCMInControl
CGCM-DLR Control
0=No, 1=Yes
BOOL
7
Spare1
CGCM-DLR is active in a redundant pair
0=False, 1=True