Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
111
CGCM-DLR Unit Configuration
Chapter
4
Related Parameters
•
GenVT_Config
•
BusVT_Config
•
GenRated_V
Load Share Page
The Load Share page is used to configure the unit parameters that are related to
the real power load-sharing function of the unit.
•
Full Scale Voltage - Sets the load share output voltage when the generator is
producing rated real power. The tag
LS_FS_V
in the configuration table
stores this value, expressed in volts.
•
Limit - Sets the maximum per unit load share error reported to the host
controller. The tag
LSLimit
in the configuration table stores this value,
expressed in per unit power.
•
Rate - Sets the maximum change in the load share error per CGCM-DLR
unit update cycle. The tag
LSRate
in the configuration table stores this
value, expressed in seconds per rated watts.
Related Parameters
•
GenRated_W