Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
83
CGCM-DLR Unit Configuration
Chapter
4
4.
In the Module Properties dialog box, click Internet Protocol.
5.
Select 'Manually configure IP settings' under Internet Protocol (IP)
Settings.
6.
Set the Physical Module IP address, Subnet Mask, and Gateway Address to
Enterprise compatible addresses.
In this example, the IP address is changed from 192.168.1.114 to
10.90.172.72.
7.
Click Set.
IMPORTANT
If the option to select 'Manually configure IP settings' is grayed out,
verify that the thumbwheel switches on the CGCM-DLR unit have been
set to 99 and the unit has been power-cycled. If you had to set the
thumbwheel switches, then close and reopen the Module Properties
window.
IMPORTANT
A notice appears that states the IP address in the physical module does
not match the address in general properties.