CGCM-DLR Unit Software Interface
Chapter 6
For instance, a 30 MVA machine operating at 10% load yields an energy tag limit
of:
(8,338,600 * 0.1 * 30000) = 25,015,800,000 kVAh, or 2.50158 x 10
10
kVAh
When the energy tag value exceeds 8,338,600, rounding of the value begins to
occur.
The energy values are not retentive. When the CGCM-DLR unit powers up or
re-establishes a connection with the controller, the energy presets in the
Unscheduled Write table are written to the energy metering values.
Data Table
Table 12 - Unscheduled Read Data Table, Assembly Instance 5
Byte
Size in
Bytes
Type
Tag Name
Description
Units
Range
0
4
Real
AvgPF
Average Power Factor
PF
-1…1
4
4
Real
PhA_PF
Phase A Power Factor
8
4
Real
PhB_PF
Phase B Power Factor
12
4
Real
PhC_PF
Phase C Power Factor
16
4
Real
Total_kVA
Total kVA
kVA
0…3E+09
20
4
Real
PhA_kVA
Phase A kVA
24
4
Real
PhB_kVA
Phase B kVA
28
4
Real
PhC_kVA
Phase C kVA
32
4
Real
PhA_kW
Phase A kW
kW
-3E+09…3E+09
36
4
Real
Ph_B_kW
Phase B kW
40
4
Real
PhC_kW
Phase C kW
44
4
Real
Total_kVAR
Total kVAR
kVAR
48
4
Real
PhA_kVAR
Phase A kVAR
52
4
Real
PhB_kVAR
Phase B kVAR
56
4
Real
PhC_kVAR
Phase C kVAR
60
4
Real
Avg_I
Average Current
A
0…60,000
64
4
Real
PhA_I
Phase A Current
68
4
Real
PhB_I
Phase B Current
72
4
Real
PhC_I
Phase C Current