112
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 4
CGCM-DLR Unit Configuration
Voltage Page
The Voltage page is used to configure the unit parameters that are related to the
voltage protection and compensation functions.
Overvoltage
•
Setpoint - Establishes the overvoltage setpoint. This setpoint is stored in
tag
Ovr_V_Setpt
in the configuration table and scaled in per cent rated
generator volts.
•
Delay - Establishes the time the generator voltage must be above the
overvoltage setpoint before the CGCM-DLR unit annunciates an
overvoltage fault. This setpoint is stored in tag
Ovr_V_TimeDly
in the
configuration table and scaled in seconds.