234
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix E
Detailed CGCM-DLR Unit Tag Descriptions
Definite Time Over-frequency Outputs from CGCM Unit
•
OvrFreqFlt
- This tag is used to communicate the occurrence of an
Over-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Definite Time Under-frequency Inputs to CGCM-DLR Unit
•
UndrFreqFltOutEn
- When this tag is a 1 in the configuration, and an
Under-frequency Fault occurs (as defined by the UndrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-frequency Condition has no effect on the Fault Relay.
•
UndrFreqSetpt
- This tag configures the generator under-frequency
setpoint at which the CGCM-DLR unit recognizes an under-frequency
condition is present and starts timing to trip based on the
Under-frequency Time Delay.
•
UndrFreqTimeDly
- This tag configures the time to
shutdown/annunciate once the generator Under-frequency setpoint has
been exceeded.
•
EngineIdle –
Setting this tag to 1 disables the under-frequency,
undervoltage, and Loss of PMG protections until the generator is at rated
speed.
Definite Time Under-frequency Outputs from CGCM
•
UndrFreqFlt
- This tag is used to communicate the occurrence of an
Under-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Reverse Power Protection Inputs to CGCM-DLR Unit
•
RevPwrFltOutEn
- When this tag is a 1 in the configuration, and a
Reverse Power Fault occurs (as defined by the Rev_kW_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, a
Reverse Power Condition has no effect on the Fault Relay.
•
Rev_kW_Setpt
- This tag configures the generator reverse kW setpoint at
which the CGCM-DLR unit recognizes a reverse power condition is
present and starts timing to trip based on the Reverse kW fault Delay
setting.
•
Rev_kW_TimeDly
- This tag configures the time to
shutdown/annunciate once the generator reverse kW setpoint has been
exceeded.