execute command
position L1
t1>tExecutionFB, then
long-operation-time in
'cause' is set
open
close
close
open
position L3
close
open
position L2
t1
tExecutionFB timer
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position
open
close
* The cmd termination will be delayed one execution sample .
*
APCtExecutionFB=IEC0
5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US
Figure 176:
tExecutionFB
The parameter
tSynchrocheck
is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
The parameter
tSynchronizing
is used to define the maximum allowed time
between the start signal for synchronizing and the confirmation that synchronizing
is in progress.
1MRK 505 394-UEN A
Section 12
Control
Line differential protection RED650 2.2 IEC
369
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...