supervised with four settable limits: low-low limit, low limit, high limit and high-
high limit. The measure value expander block (RANGE_XP) has been introduced
to enable translating the integer output signal from the measuring functions to 5
binary signals: below low-low limit, below low limit, normal, above high limit or
above high-high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose.
15.8.3
Function block
SEMOD54336-4 v3
IEC05000346-2-en.vsd
RANGE_XP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346 V2 EN-US
Figure 291:
RANGE_XP function block
15.8.4
Signals
SEMOD53803-1 v2
PID-3819-INPUTSIGNALS v5
Table 409:
RANGE_XP Input signals
Name
Type
Default
Description
RANGE
INTEGER
0
Measured value range
PID-3819-OUTPUTSIGNALS v5
Table 410:
RANGE_XP Output signals
Name
Type
Description
HIGHHIGH
BOOLEAN
Measured value is above high-high limit
HIGH
BOOLEAN
Measured value is between high and high-high
limit
NORMAL
BOOLEAN
Measured value is between high and low limit
LOW
BOOLEAN
Measured value is between low and low-low limit
LOWLOW
BOOLEAN
Measured value is below low-low limit
15.8.5
Operation principle
SEMOD52462-4 v5
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC).
The function block converts the input integer value to five binary output signals
according to
1MRK 505 394-UEN A
Section 15
Monitoring
Line differential protection RED650 2.2 IEC
589
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...