Function
Range or value
Accuracy
Independent time delay for gas
pressure alarm
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is
greater
Independent time delay for gas
pressure lockout
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is
greater
CB Contact Travel Time,
opening and closing
±3 ms
Remaining Life of CB
±2 operations
Accumulated Energy
±1.0% or ±0.5 whichever is
greater
15.5
Event function EVENT
SEMOD120002-1 v2
15.5.1
Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function
EVENT
S00946 V1 EN-US
-
15.5.2
Functionality
M12805-6 v11
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The EVENT function block is used for
LON and SPA communication.
Analog, integer and double indication values are also transferred through the
EVENT function.
1MRK 505 394-UEN A
Section 15
Monitoring
Line differential protection RED650 2.2 IEC
553
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...