18.4.8.4
Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the
Engineering Manual
.
PID-6829-INPUTSIGNALS v3
Table 467:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCINTOUT
INTEGER
0
Source to integer output
PID-6829-OUTPUTSIGNALS v3
Table 468:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
18.4.8.5
Settings
PID-6829-SETTINGS v3
Table 469:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
18.4.8.6
Operation principle
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Section 18
1MRK 505 394-UEN A
Station communication
650
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...