a>b
a
b
Counter
Rst
CU
CV
X
q
-1
÷
÷
R I
R I
a>b
a
b
0
Counter
Rst
CU
CV
q
-1
EAFPULSE
RSTACC
EAFACC
T
F
t
tOff
TP
0
q
-1
tEnergyOffPls
1000 GWh
EAFAccPlsQty
tEnergyOnPls
q
-1
= unit delay
IEC13000188-5-en.vsdx
IEC13000188 V5 EN-US
Figure 307:
Logic for pulse generation of integrated active forward energy
The maximum demand values for active and reactive power are calculated for the
set time interval
tEnergy
. The maximum values are updated every minute and
stored in a register available over communication and from outputs
MAXPAFD
,
MAXPARD
,
MAXPRFD
and
MAXPRRD
for the active and reactive power forward
and reverse direction. When the
RSTDMD
input is active from the local HMI reset
menu, these outputs are reset to zero. The energy alarm is activated once the
periodic energy value crosses the energy limit
ExLim
shows the logic
of alarm for active forward energy exceeds limit and Maximum forward active
power demand value. Similarly, the maximum power calculation and energy alarm
outputs in the active reverse, reactive forward and reactive reverse is implemented.
Average Power
Calculation
X
a>b
a
b
q
-1
T
F
0.0
tEnergy
EALim
P (ACTIVE FORWARD)
RSTMAXD
EAFALM
MAXPAFD
MAX
IEC13000189-4-en.vsd
q
-1
= unit delay
IEC13000189 V4 EN-US
Figure 308:
Logic for maximum power demand calculation and energy alarm
Section 16
1MRK 505 394-UEN A
Metering
620
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...