In the above example when integer 15 is on the input INP the OUT1 has a value
=1, OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The
sum of these OUTx is equal to 1 + 2 + 4 + 8 = 15.
This follows the general formulae: The sum of the values of all OUTx = 2
x-1
where
1≤x≤16 will be equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16) will transfer an integer with
a value between 0 to 65535 connected to the input INP to a combination of
activated outputs OUTx where 1≤x≤16. The sum of the values of all OUTx will
then be equal to the integer on input INP. The values of the different OUTx are
according to the table below. When an OUTx is not activated, its value is 0.
When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to
that integer 65535 is connected to input INP. The IB16 function is designed for
receiving the integer input locally. If the BLOCK input is activated, it will freeze
the logical outputs at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the
output OUT on the function block IB16.
Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
OUT6
BOOLEAN
Output 6
32
0
OUT7
BOOLEAN
Output 7
64
0
OUT8
BOOLEAN
Output 8
128
0
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
OUT11
BOOLEAN
Output 11
1024
0
OUT12
BOOLEAN
Output 12
2048
0
OUT13
BOOLEAN
Output 13
4096
0
OUT14
BOOLEAN
Output 14
8192
0
OUT15
BOOLEAN
Output 15
16384
0
OUT16
BOOLEAN
Output 16
32768
0
The sum of the numbers in column “Value when activated” when all OUTx (where
x = 1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be
converted by the IB16 function block.
1MRK 505 394-UEN A
Section 14
Logic
Line differential protection RED650 2.2 IEC
481
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...