Name
Type
Default
Description
INPUT9
BOOLEAN
0
Binary input 9
INPUT10
BOOLEAN
0
Binary input 10
INPUT11
BOOLEAN
0
Binary input 11
INPUT12
BOOLEAN
0
Binary input 12
INPUT13
BOOLEAN
0
Binary input 13
INPUT14
BOOLEAN
0
Binary input 14
INPUT15
BOOLEAN
0
Binary input 15
INPUT16
BOOLEAN
0
Binary input 16
PID-4127-OUTPUTSIGNALS v3
Table 266:
WRNCALH Output signals
Name
Type
Description
WARNING
BOOLEAN
OR function betweeen inputs 1 to 16
14.5.5
Settings
PID-4127-SETTINGS v3
Table 267:
WRNCALH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
14.5.6
Operation principle
GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2
The logic for group warning WRNCALH block is provided with 16 input signals
and 1 WARNING output signal. The function block incorporates internal logic OR
gate in order to provide grouping of connected input signals to the output
WARNING signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
WARNING
³
1
200 ms
t
IEC13000192-1-en.vsd
INPUT1
INPUT16
IEC13000192 V1 EN-US
Section 14
1MRK 505 394-UEN A
Logic
456
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...