open (NO) shall be connected to the
CBCLOSED
and
START
inputs. Then the
circuit breaker status change from closed to open will generate an auto reclosing
start pulse of limited length (100ms) subject to the usual auto recloser checks. The
auto reclosing sequence continues then as usual. Signals from manual tripping and
other functions, which shall prevent auto reclosing, need to be connected to the
INHIBIT
input. The logic for start from circuit breaker open position is shown in
.
The function can also be set to proceed to the next reclosing shot (if selected) even
if the external start signal is not received but the breaker is still not closed. The user
can set a required time delay for the auto recloser to proceed without a new start
with setting
tAutoContWait
. Also the synchrocheck conditions not fulfilled will
also make the auto recloser to proceed to next shot. This automatic proceeding of
shots is controlled by setting
AutoContinue
and is shown in figure
.
IEC16000156-1-en.vsdx
t
tAutoContWait
AND
commandCloseCB
S
R
AND
AND
OR
cbClosed
OR
synchroCheckOK
AutoContinue
AND
autoInitiate
IEC16000156 V1 EN-US
Figure 155:
Automatic proceeding of shots
Blocking, resetting and inhibiting auto reclosing
GUID-82719FE0-02E4-48FB-9685-2146480F3653 v1
The
BLKON
input is used to block the auto recloser for example, when certain
special service conditions arise. The auto recloser can also be blocked by an
unsuccessful reclosing attempt. This is controlled by the setting
BlockByUnsucCl
.
When the auto recloser is blocked it immediately resets to its initial conditions and
the
ACTIVE
output is unactivated. The
BLOCKED
output indicates that the auto
recloser is blocked. To unblock the auto recloser the
BLKOFF
input must be
activated.
The
RESET
input is used to reset the auto recloser to its initial conditions. When
initial starting conditions are fulfilled again, after a reset, the auto recloser is ready
for a new reclosing sequence.
If the
INHIBIT
input is activated it is reported on the
INHIBOUT
output. To ensure
reliable interruption and temporary blocking of the auto recloser a reset time delay
tInhibit
is used. The auto recloser will be blocked the time set in
tInhibit
after the
deactivation of the
INHIBIT
input. The following internal inhibit signals are also
affected by the setting
tInhibit
:
Section 12
1MRK 505 394-UEN A
Control
334
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...