Each auto reclosing function can be configured to co-operate with the
synchrocheck function.
12.2.3
Function block
M12633-3 v6
IEC06000189-3-en.vsd
SMBRREC
ON
OFF
BLKON
BLKOFF
RESET
INHIBIT
START
STARTHS
TRSOTF
SKIPHS
ZONESTEP
TR2P
TR3P
THOLHOLD
CBREADY
CBCLOSED
PLCLOST
SYNC
WAIT
RSTCOUNT
MODEINT
BLOCKED
SETON
READY
ACTIVE
SUCCL
UNSUCCL
INPROGR
1PT1
2PT1
3PT1
3PT2
3PT3
3PT4
3PT5
PERMIT1P
PREP3P
CLOSECB
WFMASTER
COUNT1P
COUNT2P
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ABORTED
SYNCFAIL
INHIBOUT
IEC06000189 V3 EN-US
Figure 151:
SMBRREC function block
12.2.4
Signals
PID-6796-INPUTSIGNALS v2
Table 171:
SMBRREC Input signals
Name
Type
Default
Description
ON
BOOLEAN
0
Switch AR On (at ExternalCtrl = On)
OFF
BOOLEAN
0
Switch AR Off (at ExternalCtrl = On)
BLKON
BOOLEAN
0
Set AR in blocked state
BLKOFF
BOOLEAN
0
Release AR from blocked state
RESET
BOOLEAN
0
Reset AR to initial conditions
INHIBIT
BOOLEAN
0
Interrupt and inhibit reclosing sequence
START
BOOLEAN
0
Start reclosing sequence
STARTHS
BOOLEAN
0
Start high-speed reclosing without synchrocheck
TRSOTF
BOOLEAN
0
Continue to shots 2-5 at a trip from switch-on-to-
fault
SKIPHS
BOOLEAN
0
Skip high speed shot and continue with delayed
shots
Table continues on next page
Section 12
1MRK 505 394-UEN A
Control
322
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...