PID-3924-SETTINGS v7
Table 11:
TRM_9I_3U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
1 - 10
A
1
1
Rated CT secondary current
CTprim4
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
1 - 10
A
1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
1 - 10
A
1
1
Rated CT secondary current
CTprim6
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
1 - 10
A
1
1
Rated CT secondary current
CTprim7
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint8
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec8
1 - 10
A
1
1
Rated CT secondary current
CTprim8
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint9
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec9
1 - 10
A
1
1
Rated CT secondary current
CTprim9
1 - 99999
A
1
3000
Rated CT primary current
VTsec10
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim10
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec11
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
Table continues on next page
Section 3
1MRK 505 394-UEN A
Analog inputs
54
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...