action. FAN is equal to disturbance number, which is incremented for each
disturbance.
ASDU26 / ASDU31
When a disturbance has been selected by the master by sending ASDU24, the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is just as FAN, equal to disturbance number.
Interoperability, physical layer
M11874-482 v3
Supported
Electrical Interface
EIA RS-485
Yes
number of loads
32
Optical interface
glass fibre
Yes
plastic fibre
Transmission speed
9600 bit/s
Yes
19200 bit/s
Yes
Link Layer
DFC-bit used
Yes
Connectors
connector F-SMA
No
connector BFOC/2.5
Yes
Interoperability, application layer
M11874-524 v3
Supported
Selection of standard ASDUs in monitoring direction
ASDU
Yes
1
Time-tagged message
Yes
2
Time-tagged message with rel. time
Yes
3
Measurands I
Yes
4
Time-tagged message with rel. time
Yes
5
Identification
Yes
6
Time synchronization
Yes
8
End of general interrogation
Yes
9
Measurands II
Yes
Table continues on next page
1MRK 505 394-UEN A
Section 18
Station communication
Line differential protection RED650 2.2 IEC
737
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...