2.2
Back-up protection functions
GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13
IEC 61850 or
function name
ANSI
Function description
Line Differential
RED650 (A11)
Current protection
PHPIOC
50
Instantaneous phase overcurrent protection
1
OC4PTOC
51_67
1)
Directional phase overcurrent protection, four steps
1
EFPIOC
50N
Instantaneous residual overcurrent protection
1
EF4PTOC
51N
67N
2)
Directional residual overcurrent protection, four steps
1
LCPTTR
26
Thermal overload protection, one time constant, Celsius
1
LFPTTR
26
Thermal overload protection, one time constant, Fahrenheit
1
CCRBRF
50BF
Breaker failure protection
1
CCPDSC
52PD
Pole discordance protection
1
Voltage protection
UV2PTUV
27
Two step undervoltage protection
1
OV2PTOV
59
Two step overvoltage protection
1
ROV2PTOV
59N
Two step residual overvoltage protection
1
Frequency protection
SAPTUF
81
Underfrequency protection
1
SAPTOF
81
Overfrequency protection
1
SAPFRC
81
Rate-of-change of frequency protection
1
1) 67 requires voltage
2) 67N requires voltage
2.3
Control and monitoring functions
GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15
IEC 61850 or
function name
ANSI
Function description
Line differential
RED650 (A11)
Control
SESRSYN
25
Synchrocheck, energizing check and synchronizing
1
SMBRREC
79
Autorecloser
1
QCBAY
Bay control
1
LOCREM
Handling of LR-switch positions
1
LOCREMCTRL
LHMI control of PSTO
1
Table continues on next page
Section 2
1MRK 505 394-UEN A
Available functions
42
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...