22.2.8.2
Design
M1819-3 v4
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure
This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section
xx00000299.vsd
2
1
3
Output module
IEC00000299 V1 EN-US
Figure 381:
Relay pair example
1 Output connection from relay 1
2 Output signal power source connection
3 Output connection from relay 2
1MRK 505 394-UEN A
Section 22
IED hardware
Line differential protection RED650 2.2 IEC
825
Technical manual