GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Table 375:
VMSQItechnical data
Function
Range or value
Accuracy
Voltage positive sequence, U1
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage zero sequence, 3U0
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage negative sequence, U2
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.5 degrees at U ≤ 50 V
±
0.2 degrees at U > 50 V
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
Table 376:
VNMMXU technical data
Function
Range or value
Accuracy
Voltage
(5 to 175) V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle
(5 to 175) V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
15.2
Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
15.2.1
Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function
SSIMG
-
63
15.2.2
Functionality
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit
breaker is used as input signals to the function. In addition, the function generates
alarms based on received information.
Section 15
1MRK 505 394-UEN A
Monitoring
532
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...