4 Specifications
4.3.3 Switch Settings
4-8
4.3.3 Switch Settings
The following table shows the switch settings of the MP2100.
(1) Mode Switch 1 (S1)
(2) Mode Switch 2 (S2)
* Set the CP number allocated to the communication process logic port. When using two or more
MP2100s, set different CP number.
(3) Reset Switch
This switch resets the MP2100.
This switch can be used to turn ON and OFF the MP2100 power without turning the host computer ON and OFF.
Mode Switch 1
Mode Switch 2
Reset Switch
1
2
ON
2
3
4
5
6
1
No.
Name
Status
Function
Factory
Setting
Details
1
INIT
ON
Memory Clear
OFF
Set to ON to clear memory. If this switch is set
to OFF, the program stored in flash memory will
be executed.
OFF
Normal operation
2
STOP
ON
User program stopped
OFF
Stops the user program execution. Enabled only
when the power is turned ON.
OFF
User program running
No.
Name
Status
Function
Factory
Setting
Details
1
TEST
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
2
MON
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
3
CNFG
ON
Configuration mode
OFF
Set to ON to execute self-configuration for
connect devices.
OFF
Normal operation
4
SUP
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
5
SLOT0
SLOT
1
ON
ON
OFF
OFF
- SLOT0
- ON
- OFF
- ON
- OFF
CP4
CP3
CP2
CP1
OFF
Use to set CP number.
∗
6
SLOT1
OFF