Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual
Revision 1 - MAY 2023
153
TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshooting
Ref.
No�
Display
Description
Possible Causes
Solutions
Condition
Alert, Error or Fault
3
NO AC POWER
No AC Input Power
Advisory only.
AC power is shut off at the
source (breaker) or is not
connected. The AC power
switch on the operator
(lower rocker switch) is
turned off, or the circuit
breaker on the operator
has tripped.
1. Turn AC power switch on
or connect power to the
operator.
2. Reset the operator circuit
breaker or connect power
to AC switch.
3. Reset circuit breaker at
electrical panel.
4. Have a licensed electrician
check the wiring.
4
LOW 24VDC
Low 24VDC UPS
Batteries
Advisory only.
Occurs when the battery
voltage has dropped to less
than 22V. At this level, the
batteries are 80% depleted.
Normal function until 21V.
1. No AC Power. See item 3
above.
2. Wiring / Connector problem
– check all connections.
Clean or repair as required.
3. Check battery condition.
4. SmartDC Controller charger
failure – check charger
voltage and replace
SmartDC Controller.
5. Transformer failure –
replace Transformer.
5
DEAD BATTERY
Extremely low UPS
batteries – no automatic
operation – batteries
below 21V.
Occurs when the battery
voltage has dropped to less
than 21V. At this level, the
batteries are 90% depleted.
The gate will automatically
open or close depending
upon the setting chosen.
Refer to AP (#) AC LOSS -
UPS FAIL OPEN in
automatic function is
possible, but limited push-
button control is available
to 18V.
1. No AC Power. See item 3
above.
2. Wiring / Connector problem
– check all connections.
Clean or repair as required.
3. Check battery condition.
4. SmartDC Controller charger
failure – check charger
voltage and replace
SmartDC Controller.
5. Transformer failure –
replace Transformer.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...