INSTALLER MENU FUNCTIONS
Table 6. SmartDC Controller - Installer Menu Functions
Ref.
No�
Installer Menu
Setting Options
(
Bold
= Factory Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
19
RT 0 (80 SECS)
MAXIMUM RUN TIMER
Not used in Kinetic
operators.
--
(N/A)
20
PO 0 (OFF)
PARTIAL OPEN
0 = OFF
7 = 7 ft., 8 = 8 ft., through
32 = 32 ft.
Sets the distance (from the closed gate
position) where the gate stops in a
partial open. When a number is entered
in the PO display, the open partial input
becomes operational.
OPEN PARTIAL
COM
21
EC 0 (STOP ONLY)
EYE CLOSE LOGIC
0 = Close eye stops only
1 = 2s reverse to open
2 = Full Open
The default setting is non-reversal if the
close photo eye is triggered. A setting of
1 causes the gate to reverse and travel
open for two seconds if triggered while
closing. A setting of 2 reverses the gate to
full open.
Sensor
Common
Sensor Input
22
EO 0 (STOP ONLY)
EYE OPEN LOGIC
0 = Open eye stops only
1 = 2s reverse to close
The default setting is non-reversal if the
open photo eye is triggered. A setting of
1 causes the gate to reverse travel and
close for two seconds if triggered while
opening.
Sensor
Common
Sensor Input
23
GC 1 NC CONTACT
GATE EDGE OUTPUT
0 = Normally Open Edge
1 = Normally Closed
This menu item only appears when UC
is set to 4. Default setting is edge sensor
with Normally Closed (NC) output.
Optional setting of 0 requires an (NO)
output.
Sensor
Common
Sensor Input
24
GR 0 (FULL OPEN)
GATE EDGE LOGIC
0 = Edge reverses full
open
1 = 2s reversal only
The default setting is a full-open reversal
if the gate edge is triggered while closing.
The optional setting of 1 causes the gate
to reverse for 2 seconds if triggered while
closing.
Sensor
Common
Sensor Input
25
SR 1 REVERSE 2S
IES SENSOR LOGIC
0 = IES reverses full open
1 = 2 second reversal only
The default setting is a two-second
duration reversal if the inherent sensor
is triggered. The optional setting of 0 will
cause the gate to reopen fully if triggered
while closing.
N/A
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...