154
wallaceperimetersecurity.com
Phone: 866.300.1110
TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshooting
Ref.
No�
Display
Description
Possible Causes
Solutions
Condition
Alert, Error or Fault
6
HYSECURITY
BAD POWER
Critically low 24V supply
power. This message can
occur only on initial start
up if power is critically
low.
DC power is below 14V –
no control functions will be
allowed at all.
1. No AC Power. See item 3
above.
2. Wiring / Connector problem
– check all connections.
Clean or repair as required.
3. Check battery condition.
Check power board power
switch for 115V or 230V and
match to incoming power.
7
No display. LED
blinking.
SmartDC Controller is
receiving power, but
battery voltage is very
low.
Several possible causes:
- The AC power has been
shut off from the operator
for too long and the
batteries are drained.
- Wiring problem.
- Batteries no longer hold a
charge.
- Bad SmartDC Controller.
- Bad transformer.
1. No AC power. See item 3
above.
2. Wiring / Connector problem
– check all connections.
Clean or repair as needed.
3. Check battery condition.
4. SmartDC Controller charger
failure – check charger
voltage and replace
SmartDC Controller.
5. Transformer failure –
replace transformer.
8
HYSECURITY
LOADER
The SmartDC Controller
cannot locate the
system software or
software is being loaded
into the SmartDC
Controller.
There is no software loaded
on the SmartDC Controller
or software is currently
being loaded.
Load the latest software
version (H5.XX) using S.T.A.R.T.
with a download cable
(preferably USB) or wait for
software to finish loading.
9
ALERT 1
FORCE OPEN
Gate forced open.
The gate has been forced
open from a full closed
limit and is being prevented
from re-closing. Must be
enabled in User Menu.
Will self-clear after an open or
close input.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...