Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual
Revision 1 - MAY 2023
155
TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshooting
Ref.
No�
Display
Description
Possible Causes
Solutions
Condition
Alert, Error or Fault
10
ALERT 2
DRIFT CLOSED
Gate drifted closed.
The gate has been forced
off its open limit and is
being prevented from re-
opening. Must be enabled
in User Menu.
Will self-clear after an open or
close input.
11
ALERT 3
EXCESS DRIFT
Gate drift in transit -
Advisory only.
The alert appears if the
gate drifts three times in a
five-minute period.
Check the track to make sure
it is level.
12
ALERT 4
MOTOR
OVERLOAD
Thermal overload
alert. When the alert is
triggered, the gate can
only “fully open” until
the alert is cleared.
Motor drive heat sink
exceeds 210⁰F (98.89⁰C).
The alert will temporarily
disable the operator, but
will automatically reset
itself when it cools down.
Check gate hardware,
weight/length of gate. Alert
automatically clears when
the temperature drops below
threshold.
13
ALERT 5
BOTH LIM
ACTIVE
Not used in Kinetic
operators.
N/A
N/A
14
ALERT 6
LIM NOT
RELEASED
Not used in Kinetic
operators.
N/A
N/A
15
ALERT 7
FREQ SHIFT
FAULT
The HY5B has detected
a frequency change
outside the normal
range.
Likely causes are poor
integrity of loops or
metallic objects within
range. This message
will also indicate which
detector the alert applies
to: Exit Loop (ELD), Inside
Obstruction Loop (IOLD),
Outside Obstruction Loop
(OOLD), or Center Loop
(CLD) - (User Relay 22).
The loop lead in wires and
roadway should be checked for
problems or replaced.
16
ALERT 8
LOOP SHORTED
The HY5B has detected a
loop shorted to ground.
Caused by inadequate
insulation of loop wires.
The loop lead in wires and
roadway should be checked for
problems or replaced.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...