INSTALLING VEHICLE DETECTORS AND LOOPS
9. This guide is written from a design perspective, but installation workmanship practices are equally
important to ensure proper operation and long loop life. The best way to ensure a quality installation
is to employ a professional installer experienced with detector loops. A few important practices are:
•
The slot in the surface of the road should be cut ¼-inch wide x 1½-inch deep (6.3 x 38.1mm).
• The corners of the cut must be at an angle or core drilled to relieve stress on the wires.
•
After the wire is installed, the slot must be completely backfilled with a non-hardening sealer. If
the loop wires are able to move in the slot after the sealer has set, the detector may give false
calls.
Figure 40. Loop Sealant Application
Detector Logic
HySecurity recommends that vehicle detectors be used for free open and obstruction sensing logic only.
Because of their slower speeds, closing logic is a poor choice for security gate systems. Since there are
several ways that the gate may be left standing open and because there is a loss of safety, our circuit has
not been designed to accommodate “detect to close” logic.
Loop Diagnostics
The following tests cannot guarantee a functioning loop, but failure of either test means that the loop is
definitely suspect, even though it may still be functioning at the time.
1.
Test the resistance of the loop and lead-in wire. It should not exceed 4 ohms.
2.
Test the resistance between the loop and earth ground with a 500V Megohmmeter. It should be 100
Megohms or more. Loops may function at less than 100 Megohms but will not be reliable (e.g.
,
when
the ground is wet from rainfall). Low resistance indicates broken or moisture
-
saturated insulation.
This is common if inappropriate wire insulation has been used.
A schematic for a slide gate loop layout is shown in Figure 41.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...