VEHICLE DETECTOR AND LOOP FAULT DIAGNOSTICS
Vehicle Detector and Loop Fault Diagnostics
If HY5B vehicle detector modules are used, the SmartDC Controller has the ability to store and report
detector and loop fault information for performance diagnostics.
If the SmartDC Controller senses a loop or detector problem:
•
The LCD display flashes the name of the affected detector or error and the appropriate alert code.
•
The buzzer chirps continuously at regular intervals until the issue is resolved.
Table 13. HY5B Vehicle Loop Detector Faults and Errors
Alert or Error
#
LCD Description
Advisory
Resolution
ALERT 7
FREQ SHIFT FAULT
HY5B vehicle detector –
Abnormal frequency change
alert.
The alert indicates an unstable loop
frequency. Check the loop and lead-in wires
for problems. Replace them, if necessary.
ALERT 8
LOOP SHORTED
HY5B vehicle detector –
Loop is shorted.
The alert indicates that the loop and lead
-
in wires are shorting out. Check the wires
for problems. Replace them, if necessary.
ALERT 9
LOOP OPEN
HY5B vehicle detector -
Disconnected loop alert.
The alert indicates the loop wires are
loose or disconnected. Check the wires
for problems. Replace them, if necessary.
ALERT 10
I²C BUSS ERROR
HY5B vehicle detector -
Communications alert.
The alert indicates the detector is not
communicating properly with the SmartDC
Controller. The alert occurs if the detector
is unplugged or the connection is unstable.
If communication is not re
-
established
within 30 seconds, the controller will reset
and the message changes to ERROR 3.
ALERT 11
DETECTOR FAULT
HY5B vehicle detector -
Malfunction alert.
The display indicates the HY5B
detector malfunction. Check detector
for problems. Replace it, if necessary.
ALERT 12
ON TOO LONG
Detector input triggered too
long –
More than five minutes.
The display indicates the HY5B detector
malfunction. The alert also works for any
input connected to the terminal strip for
standard box detectors. Check that a vehicle
is not parked on the loop. Also, determine
if the loop is stable. An unstable loop can
hold the detector in a triggered state.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...