USER MENU FUNCTIONS
Table 5. SmartDC Controller - User Menu Functions
Ref.
No�
User Menu
Setting Options
(
Bold
= Factory
Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
10
DS 0 (OFF)
DIAGNOSTIC LOGS
0 = off (standard)
1 = on (detailed)
Set this item to 1 to record all gate operator
open and close events, in addition to the
normal alert, fault and error logs. This
parameter automatically resets to the
default 0 (off) after 24 hours, which is useful
when experiencing intermittent problems.
Set to 0, the DC Controller logs pertinent
gate operator events such as faults, errors, or
menu manipulation.
USB or
RS232 cable
and laptop
computer with
HySecurity’s
free S.T.A.R.T.
software is
required to
read the log
file.
11
FA 0 (OFF)
FORCE OPEN ALERT
0 = off
1 = on
Intended for highly secure facilities.
Set to 1, the operator sounds the 3-second
“warn before operate” buzzer alarm, and
then initiates a closure if the gate is forced
open and the closed limit switch disengages.
The motor restarts to secure the gate. If the
gate does not fully close within 4 seconds,
the motor turns off and the alert buzzer
sounds for 30 seconds. The display shows
ALERT 1 – FORCED OPEN.
(N/A)
12
DA 0 (OFF)
DRIFT CLOSE ALERT
0 = off (standard)
1 = on
Set to 1, the operator sounds the 3-second
“warn before operate” buzzer alarm and
initiates an open command if the gate is
forced, or drifts, off the open limit switch.
The motor starts to reopen the gate. The
motor runs for a maximum of 4 seconds and,
if the gate is not fully open at the end of this
period, the buzzer sounds for 10 seconds.
The display shows ALERT 2 – DRIFT CLOSED.
(N/A)
13
LG 0 (OFF)
VIEW EVENT LOG
0 = off
1 = on
With v5.53 (or later) software, you can set
LG to 1 and view abbreviated event logs on
the display. These messages are helpful for
diagnostic purposes and reviewing the gate
operator’s event history. Over 300 events
can be logged before the software begins
overwriting the existing history.
(N/A)
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...