ENABLING THE FIRE DEPARTMENT OVERRIDE
Many counties and cities require a Fire Department
override system for gate operators. The fire
department’s alert system is a separate unit that
must be connected to the Smart DC Controller. The
FIRE DEPARTMENT OPEN option must be properly
configured through the Installer Menu before the
operator will recognize the alert system.
To adjust the Fire Department Override, take the
following steps:
1�
Connect the contact NO from the alert system
or key switch to the following SmartDC
Controller terminals:
EMERG OPEN
+24V
2�
Configure the Installer Menu.
At a gate status display, press the MENU
button twice. This accesses the User Menu
and the CLOSE TIMER display appears.
3�
Simultaneously, press the OPEN and RESET
buttons to enter the Installer Menu. Release
the buttons and the LEARN LIMIT display
appears.
4�
Press NEXT until the FIRE DEPARTMENT
OPEN display appears. The factory default
setting is 0.
5�
Use the NEXT button to change the number
on the display to 1 and then press SELECT.
6�
To exit the Installer Menu, press the MENU
button. The gate status appears in the display
indicating you have returned to Run Mode.
Enabling the Fire Department Override
1. Start at a gate status
display.
2. To access the User
Menu, press MENU
twice.
3. To access the Installer
Menu, simultaneously
press OPEN and RESET.
4. Use NEXT to navigate
to the menu display.
Change the setting using
the SELECT and NEXT
buttons.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...