Function Parameter Table VD520 Series Inverter User Manual
- 62 -
F8-10
Over current
Stall Proportion
Gain
0: Disabled
1~1000
20
○
F8-11
Over current
Stall Integral
Gain
0~1000
20
○
F8-12
Over current
Stall Protection
Current
100%~200%
160%
○
F8-13
Quick Start Over
current
Suppression
Gain
0~100
30
○
F8-14
Short-circuit to
Ground Upon
Power-on
0: Invalid
1: Valid
1
○
F8-15
Input Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
○
F8-16
Output Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
◎
F8-17
Offload
Protection
Selection
0: Invalid
1: Valid
0
○
F8-18
Offload
Detection Level
0.0~100.0%
10.0%
○
F8-19
Offload
Detection Time
0.0s~60.0s
1.0s
○
F8-24
Action Selection
Upon
Instantaneous
Power Failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
○
F8-25
Voltage Restore
Judgment Value
Upon
Instantaneous
Power Failure
F0-10~100.0%
90.0%
○
F8-26
Voltage Restore
Judgment Time
Upon
Instantaneous
Power Failure
0.00s~100.00s
0.50s
○
F8-27
Voltage
Judgment Value
Upon
Instantaneous
Power Failure
60.0%~100.0% (Standard bus
voltage)
80.0%
○
Содержание VD520 Series
Страница 2: ......
Страница 9: ...VD520 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce ...