Parameter Description VD520 Series Inverter User Manual
- 104 -
F0-22
Command Source
Bound Frequency
Source
Unit’s digit: Operation panel command binding
frequency source selection
0: No binding
1: Digital setting frequency
2: AI1
3: AI2
4: Reserved
5: PULSE setting
6: MS reference
7: Simple PLC
8: PID
9: Communication setting
Ten’s digit: terminal command binding frequency
source selection, same as above
Hundred’s digit: communication command binding
frequency source selection, same as above
Thousand’s digit: Automatic operation command
binding frequency source selection, same as
above
0x0000
○
Define the bound combination between three run command channel and nine kinds of frequency
given channel, convenient to realize synchronous switch.
The meaning of the above frequency for given channel is same with the main frequency source X
selection F0-02, please see the description of F0-02 function code.
The different run command channels can be bound to the same frequency given channel.
When the command source has bundled frequency source, during the effective period of this
command source, the set frequency source of F0-02~F0-07 is no longer work.
F0-23
Communication
Protocol Selection
0: Modbus
0
●
See chapter 9 communication protocol description.
F0-24
Motor Selection
0: Motor 1
1: Motor 2
0
◎
VD520 supports the application of frequency inverter time-sharing drag 2 motor respectively,
electrical motor nameplate parameters can be set respectively by 2 motor, independent parameters
tuning, select different control modes, independent setting parameters related to run performance etc.
Motor 1 corresponding function parameter is F2 and F3 group, motor 2 corresponding function
parameter A3 group.
The user through the F0-24 function code to select current motor, also can through the digital quantity
input terminals DI switch motor. When function code selection and terminal selection contradiction,
the terminal selection shall prevail.
F0-25
GP Type Selection
1: G type (constant torque load model)
2: P type (fan, pump type load models)
1
◎
1: Is suitable for the constant torque load of specified rated parameters.
2: Is suitable for the variable torque load of specified rated parameters (fan, pump).
Содержание VD520 Series
Страница 2: ......