Parameter Description VD520 Series Inverter User Manual
- 124 -
F5-01
DI1 Input Terminal
Function Selection
0~63, see table blow
1
◎
F5-02
DI2 Input Terminal
Function Selection
2
◎
F5-03
DI3 Input Terminal
Function Selection
4
◎
F5-04
DI4 Input Terminal
Function Selection
6
◎
F5-05
DI5 Input Terminal
Function Selection
8
◎
F5-06
HDI1 Terminal Function
Selection
0
◎
This parameter is used to set the functions of the multifunctional digital input terminals.
Set
Value
Function
Description
0
No function
The termin
als not being used can be set “no function”, to avoid
wrong operation.
1
Forward running
Via external terminals to control inverter forward reverse run
2
Reverse running
3
Three-line run control
Via this terminal to confirm the inverter run mode is 3line run or
alternative control mode. Refer to the function code F5-00
(“terminal command mode”) description.
4
Forward Jog(FJOG)
FJOG is jog forward run, RJOG is jog reverse run. Jog run
frequency, jog Acceleration/down time refer to function code
Fb-00, Fb-01, Fb-02 description.
5
Reverse Jog(RJOG)
6
Coast to stop
Inverter block output, at present motor stop is not controlled by
inverter. This method is the same as F1-08 described coast to
stop.
7
Run pause
Inverter deceleration stop, but all run parameter is in memory
state. Such as PLC parameters, swing frequency parameters,
PID parameters. After this terminal signal disappears, inverter
back to running state before the parking.
8
Fault reset (RESET)
Using terminal function to reset error, the same function as
keypad RESET. This function can realize long distance error
reset.
9
External fault input
When external error signal pulse sent to inverter, inverter alarm
error Err.17, and according to the fault protection action
approach to trouble shooting (details refer to the function code
F9-36).
10
External fault normally
closed input
After the external fault normally closed signal into frequency
inverter, inverter report fault Err.17 and downtime.