Parameter Description VD520 Series Inverter User Manual
- 140 -
F8 Protection Parameters
F8-00
Motor 1 Overload
Protection Selection
0: Disabled
1 : Enabled
1
○
F8-01
Motor 1 Overload
Protection Gain
0.20~10.00
1.00
○
F8-00=1: no motor overload protection function, there may be a motor overheating damage risk,
suggest adding thermal relay between inverter and motor.
F8-00=1: inverter according to the motor overload protection inverse time curve detemine whether the
motor overload at this moment.
Inverse time curves of the motor overload protection are as follows: 220% X (F8-01) X rated motor
current, last 1 minute alarm motor overload fault; 150% X (F8-01) X rated motor current, last 60
minutes alarm motor overload.
User needs according to the actural overload capacity of motor, set up the F8-01 value correctly, if set
the parameter is too big easy to cause the damage of motor overheating, and inverter is not alarm.
F8-02
Motor 1 Overload
Warning Coefficient
50%~100%
80%
○
This function is used to in the front of the motor overload fault protection, through the DO give a
warning signal to control system. The warning coefficient used to detemine how much to warning
before the motor overload protection. The greater the value, the smaller the warning advance.
When the inverter output current cumulants is greater than the product of overload inverse time curve
with F8-02, inverter multi-function digital DO output the
“motor overload warning” ON signal.
F8-03
Motor 2 Overload
Protection Selection
0: Disabled
1 : Enabled
0
○
F8-04
Motor 1 Overload
Protection Gain
0.20~10.00
1.00
○
F8-05
Motor 1 Overload
Pre-alarm Coefficient
50%~100%
80%
○
Same as motor 1 overload protection parameter.
F8-06
Overvoltage/over current
Stall Mode Selection
0: Mode 0
1: Mode 1
≤11kW: 1
◎
>11kW: 0
F8-07
Overvoltage Stall
Proportion Gain
0: Disabled
1~100
10
○
F8-08
Overvoltage Stall Integral
Gain
0~100
5
○
F8-09
Overvoltage Stall
Protection voltage
100.0VDC~800.0VDC
380VAC: 700.0VDC
○
220VAC: 370.0VDC
In the process of frequency converter to slow down, when DC bus voltage more than the overvoltage
stall protection voltage, frequency converter to stop deceleration to keep on the current running
frequency, after waiting for bus voltage drops to continue to deceleration.
Overvoltage stall gain, used to adjust in the process of deceleration, inverter overvoltage control