VD520 Series Inverter User Manual Function Parameter Table
- 61 -
Display
Parameters
F7-07
Load Speed
Display
Coefficient
0.000s~6.5000
1.0000
○
F7-08
Load Speed
Display Decimal
Places
0: 0 bit decimal place
1: 1 bit decimal place
2: 2 bit decimal place
3: 3 bit decimal place
1
○
F8 Protection Parameters
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
F8-00
Motor 1
Overload
Protection
Selection
0: Disabled
1 : Enabled
1
○
F8-01
Motor 1
Overload
Protection Gain
0.20~10.00
1.00
○
F8-02
Motor 1
Overload
Warning
Coefficient
50%~100%
80%
○
F8-03
Motor 2
Overload
Protection
Selection
0: Disabled
1 : Enabled
0
○
F8-04
Motor 1
Overload
Protection Gain
0.20~10.00
1.00
○
F8-05
Motor 1
Overload
Pre-alarm
Coefficient
50%~100%
80%
○
F8-06
Overvoltage/ove
r current Stall
Mode Selection
0: Mode 0
1: Mode 1
≤11kW: 1
◎
>11kW: 0
F8-07
Overvoltage
Stall Proportion
Gain
0: Disabled
1~100
10
○
F8-08
Overvoltage
Stall Integral
Gain
0~100
5
○
F8-09
Overvoltage
Stall Protection
voltage
100.0VDC~800.0VDC
380VAC: 700.0VDC
○
220VAC: 370.0VDC