Parameter Description VD520 Series Inverter User Manual
- 180 -
b0-30
User Code 30
FF-06
○
b0-31
User Code 31
FF-06
○
This function code is the users customize parameter group.
Users can in all VD520 function code, select the needed parameter summary to b0 group, as the user
customization parameters, convenient to view and change such as operation.
b0 group most provide 31 users customize parameter, b0 group parameter display value is F0.00,
said the user function code is empty.
Enter the users customize parameter mode, the display code defined by b0-00~b0-31, order
consistent with b0 group function code, will skip when for F0-00.
b1 Virtual IO Parameter Group
b1-00
Virtual VDI1 Terminal
Function Selection
0~59
0
◎
b1-01
Virtual VDI2 Terminal
Function Selection
0~59
0
◎
b1-02
Virtual VDI3 Terminal
Function Selection
0~59
0
◎
b1-03
Virtual VDI4 Terminal
Function Selection
0~59
0
◎
b1-04
Virtual VDI5 Terminal
Function Selection
0~59
0
◎
Virtual VDI1~VDI5 are exactly the same when the control panel DI on the function, can be used as a
multi-function digital quantity input, the detail setting please refer to the introduce of F5-00~F5-09.
b1-05
Virtual VDI Terminal
State Setting Mode
Unit’s digit: virtual VDI1
0: By virtual VDOx state to decide VDI is valid
or not
1: By code b1-06 setting VDI is valid or not
Ten’s digit: virtual VDI2, same as above
Hundred’s digit: virtual VDI3, same as above
Thousand’s digit: virtual VDI4, same as above
Ten thousand’s digit: virtual VDI5, same as
above
0x00000
◎
b1-06
Virtual VDI Terminal
state setting
Unit’s digit: virtual VDI1
0: Disabled
1: Enabled
Ten’s digit: virtual VDI2, same as above
Hundred’s digit: virtual VDI3, same as above
Thous
and’s digit: virtual VDI4, same as above
Ten thousand’s digit: virtual VDI5, same as
above
0x00000
◎
Different from ordinary digital quantity input terminals, the state of the virtual VDI can set two ways,
and selection by b1-05.
When selecting VDI status is decided by the state of the corresponding virtual VDO, VDI whether is
valid state, depending on the VDO output as valid or invalid, and the VDIx only binding VDOx (x is 1~
5).