Communication Protocol VD520 Series Inverter User Manual
- 200 -
Output frequency low Bit
xx H
CRC CHK low Bit
xx H
CRC CHK high Bit
xx H
END
T1-T2-T3-T4
9.6.2 Command Code: 06H (0000 0110), write one word
Such as: Put 5000(1388H) (namely write-in setting frequency 50.00Hz) write to slave address 01H
inverter 3001H (communication set frequency address). The frame structure description as below:
RTU Master command information.
START
T1-T2-T3-T4
ADDR
01H
CMD
06H
Write data address high Bit
30H
Write data address low Bit
01H
Data content high Bit
13H
Data content low Bit
88H
CRC CHK low Bit
DAH
CRC CHK high Bit
5CH
END
T1-T2-T3-T4
RTU slave response information.
START
T1-T2-T3-T4
ADDR
01H
CMD
06H
Write data address high Bit
30H
Write data address low Bit
01H
Data content high Bit
13H
Data content low Bit
88H
CRC CHK low Bit
DAH
CRC CHK high Bit
5CH
END
T1-T2-T3-T4
9.6.3 Communication Format Error Check Method
Frame error check mode includes two part verification, Bit check of byte (odd/even verify) and CRC
check of complete data of format.
9.6.3.1 Byte check
User can select different check mode according to requirement, can also select no-check, but it will
affect the Bit setting of every byte check.
Even parity check: add a Bit of even parity check before data transmission, to express the number of
“1” in the transmission data is odd or even, if the number is even, check Bit is “0”, otherwise it “1”. This