VD520 Series Inverter User Manual Function Parameter Table
- 67 -
2: Continue to run
T
en’s digit: user-defined fault 1 (36)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: power on time
reached (28)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: offload (37)
0: Coast to stop
1: Stop according to stop mode
2: Decelerate to 7% of the rated motor
frequency continue running,
automatically restored to the set
frequency operation when no offload
Ten thousand’s digit: PID feedback
lost when running (18)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
F9-39
Fault Protection
Action Selection
4
Un
it’s digit: user-defined fault (22)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: reserved
Hundred’s digit: reserved
Thou
sand’s digit: reserved
Ten t
housand’s digit: reserved
0x00000
○
F9-40
Continue
Running
Frequency
Selection at
Failure
0: Run to the current running
frequency
1: Run at set frequency
2: Run at frequency upper limit
3: Run at frequency lower limit
4: Run at abnormal standby frequency
0
○
F9-41
Abnormal
Standby
Frequency
60.0%~100.0%
(100.0% corresponding max
frequency F0-10)
100.0%
○
FA Process PID
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
FA-00
PID Given
0: FA-01 setting
0
○
Содержание VD520 Series
Страница 2: ......
Страница 9: ...VD520 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce ...