Parameter Description VD520 Series Inverter User Manual
- 132 -
11
Frequency 2 reached
output
Please refer to the instruction of function code Fb-23, Fb-24.
12
Zero speed running
1 (no output when
stop)
When frequency inverter is running and the output frequency is 0,
then output ON signal. When inverter is in a state of downtime,
the signal is OFF.
13
Zero speed running
2 (output when
stop)
When frequency inverter is running and the output frequency is 0,
then output ON signal. When inverter is in a state of downtime,
the signal also is ON.
14
Frequency upper
limit reached
When operation frequency reach to the upper limit frequency,
output ON signal.
15
Frequency lower
limit reached (about
running)
When operation frequency reach to the lower limit frequency,
output ON signal. When inverter is in a state of downtime, the
signal is OFF.
16
Frequency lower
limit reached (output
when stop)
When operation frequency reach to the lower limit frequency,
output ON signal. When inverter is in a state of downtime, the
signal also is ON.
17
Current 1 reached
output
Please refer to the instruction of function code Fb-29, Fb-30.
18
Current 2 reached
output
Please refer to the instruction of function code Fb-31, Fb-32.
19
Zero current state
Please refer to the instruction of function code Fb-25, Fb-26.
20
Output current limit
exceeded
Please refer to the instruction of function code Fb-27, Fb-28.
21
Motor overload
pre-alarm
Before overload protection, according to the overload forecasting
warning threshold value to judge, after more than forecasting
warning threshold output ON signal. Parameter set refer to the
function code F8-00~F8-02.
22
Inverter overload
pre-alarm
In the first 10s in inverter overload protection, output ON signal.
23
During the load
When frequency inverter during the load, output ON signal.
24
Set Count value
reached
When the count value reach to the set value of Fb-59, output ON
signal.
25
Designated count
value reached
When the count value reach to the set value of Fb-60, output ON
signal. Count function refer to the function instruction of Fb group.
26
Length reached
When the actural length of testing more than Fb-56 setting length,
output ON signal.
27
Module temperature
reached
Radiator temperature of inverter module (FF-11) meet the module
settings of the temperature reaches the value (Fb-39), output ON
signal.
29
Current running time
reached
When frequency inverter current running time more than the
setting time of Fb-33, output ON signal.
30
Accumulative
running time reached
When frequency inverter accumulative running time more than
the setting time of Fb-35, output ON signal.